Configurable Block Periods
0.05, 0.1, 0.2, 0.5, 0.6, 1, 2, 5, 6, 10, 30 seconds 1, 10, 60 minutes
Block Processing Cycle
0.05, 0.1, 0.2, 0.5 and 1.0 seconds, selectable at system configuration time
Time to Marry Fault-Tolerant Modules
Less than 1 second
Internal Diagnostics
Self-checking performed at power-up. Run-time checks and the watchdog timer function performed during operation.
Infrared Communications
Letterbug assignment via the Letterbug Configurator. Letterbug or Hardware ID readout via the Letterbug Configurator.
Power Requirements
INPUT VOLTAGE (REDUNDANT VOLTAGE)
24 V dc typical
CONSUMPTION (PER NON-FAULT-TOLERANT MODULE)
8.5 W, maximum
Regulatory Compliance
ELECTROMAGNETIC COMPATIBILITY (EMC)
European EMC Directive 89/336/EEC
Meets: EN 50081-2 Emission standard
EN 50082-2 Immunity standard
EN 61326 Annex A (Industrial Levels)
CISPR 11, Industrial Scientific and Medical (ISM) Radio-frequency Equipment – Electromagnetic Disturbance Characteristics – Limits and Methods of Measurement Meets Class A Limits IEC 61000-4-2 ESD Immunity Contact 4 kV, air 8 kV IEC 61000-4-3 Radiated Field Immunity 10 V/m at 80 to 1000 MHz IEC 61000-4-4 Electrical Fast Transient/Burst Immunity ±2 kV on I/O, dc power and communication lines
IEC 61000-4-5 Surge Immunity ±2 kV on ac and dc power lines; ±1 kV on I/O and communications lines IEC 61000-4-6 Immunity to Conducted Disturbances Induced by Radio-frequency Fields 10 V (rms) at 150 kHz to 80 MHz on I/O, dc power and communication lines IEC 61000-4-8 Power Frequency Magnetic Field Immunity 30 A/m at 50 and 60 Hz
PRODUCT SAFETY
Underwriters Laboratories (UL) for U.S. and Canada
UL/UL-C listed as suitable for use in UL/ULC listed Class I, Groups A-D; Division 2; temperature code T4 enclosure based systems. These modules are also UL and UL-C listed as associated apparatus for supplying non-incendive communication circuits for Class I, Groups A-D hazardous locations when connected to specified I/A Series/Foxboro Evo system Fieldbus Modules as described in the DIN Rail Mounted Subsystem User’s Guide (B0400FA). Communications circuits also meet the requirements for Class 2 as defined in Article 725 of the National Electrical Code (NFPA No.70) and Section 16 of the Canadian Electrical Code (CSA C22.1).Conditions for use are as specified in the DIN Rail Mounted Subsystem User’s Guide (B0400FA).
EUROPEAN LOW VOLTAGE DIRECTIVE 73/23/EEC AND EXPLOSIVE ATMOSPHERES (ATEX) DIRECTIVE 94/9/EC
CENELEC (DEMKO) certified as EEx nAnL IIC T4 for use in CENELEC certified Zone 2 enclosure certified as associated apparatus for supplying non-incendive field circuits for Zone 2, Group IIC, potentially explosive atmospheres when connected to specified I/A Series system Fieldbus Modules as described in the DIN Rail Mounted Subsystem User’s Guide (B0400FA).
FUNCTIONAL SPECIFICATIONS (CONTINUED)
SECURITY
Wurldtech Achilles Certification™ Level One
ENVIRONMENTAL SPECIFICATIONS(2)
Operating
TEMPERATURE:0 to +60°C (+32 to +140°F)
RELATIVE HUMIDITY :5 to 95% (Noncondensing)
ALTITUDE:-300 to +3,000 m (-1,000 to +10,000 ft)
CONTAMINATION:Class G3 (Harsh) as defined in ISA Standard, S71.04. Pollution degree 2 as defined in IEC 664-1.
VIBRATION:0.5 g (5 to 500 Hz)
Storage
TEMPERATURE:-40 to +70°C (-40 to +158°F)
RELATIVE HUMIDITY :5 to 95% (Noncondensing)
ALTITUDE:-300 to +12,000 m (-1,000 to +40,000 ft)
PHYSICAL SPECIFICATIONS
Configuration:Single processor module. The fault-tolerant version consists of two processor modules, with an interconnecting fault-tolerant connector integral to the baseplate.
Mounting:May be placed in device specific 2- or 4-position baseplates designed for horizontal or vertical mounting. For the fault-tolerant FCP270, the two modules must be mounted in dedicated slots to allow for interconnecting fault-tolerant communication.
Dimensions – Module
HEIGHT
103 mm (4.04 in)
114 mm (4.50 in) including mounting lugs
WIDTH:51.5 mm (2.03 in)
DEPTH:147 mm (5.80 in)
Mass (Maximum) :0.6 kg (1.3 lb) for a single, non-fault-tolerant module.
Fiber Optic Cabling – Ethernet Switch to FCP270
CONNECTORS
Ethernet Switch Connector
One MT-RJ Connector
FCP270 or Splitter/Combiner Connector
Two ceramic type LC connectors with clip
FIBER OPTIC CABLE
Cable Material
Multimode fiber (MMF) 62.5/125 µm plenum Cable Lengths
3 m (9.9 ft), 15 m (49.5 ft), 50 m (165 ft) greater than 50 m – user supplied
Maximum Length 2 km (6,560 ft) from the Ethernet switch to the FCP270.
Fiber Optic Cabling – Splitter/Combiner to FCP270
CONNECTORS
Two ceramic type LC connectors with clip on each end
FIBER OPTIC CABLE
Cable Material
Multimode fiber (MMF) 62.5/125 µm
Cable Lengths
0.5 m (1.6 ft), 1.0 m (3.3ft), 3.0 m (9.9 ft),
15 m (49.5 ft), 50 m (165 ft)
greater than 50 m – user supplied
Maximum Length
2 km (6,560 ft) total from the Ethernet switch to the FCP270, including the cabling to the splitter/combiner.
FCP270 Fieldbus without FCM2Fs The cable length of the Fieldbus cannot exceed 60 m (198 ft) (see Figure 4).
FCP270 Fieldbus with FCM2Fs
Each FCP/FCM drives a segment of interconnected baseplates of up to 60 m (198 ft). Up to four pairs of FCM2Fxs can be used in a Fieldbus network (see Figure 5).
FCP270 Fieldbus and Expanded Fieldbuses (1-4) without FCM2Fs The cable length of the Fieldbus cannot exceed 60 m (198 ft) (see Figure 6).
FCP270 Fieldbus and Expanded Fieldbuses (1-4) with FCM2Fs Each FCP/FCM drives a segment of interconnected baseplates of up to 60 m (198 ft). Up to four pairs of FCM2Fxs can be used in each Expanded Fieldbus network (see Figure 7).
Related product recommendations:
ABB GFD563A102 3BHE046836R0102
ABB PPD113B03 3BHE023584R2365
GE IS220PPDAH1B
ABB 3BHE041576R3011 – PPD517 A3011
ABB PPD103 3BHE020455R0001
ABB PPD113B03-26-100100 3BHE023584R2625
GE IS220PPDAH1A REV D
ABB PPD113B01-10-150000
ABB PPD113B03-26-100110
ABB PPD113B01 3BHE023784R1010
GE IS220PPDAH1A REV E
ABB PPD512A10-150000
Honeywell TC-PPD011
ABB 3BHE020455R0001 PPD103 B01
ABB PPD113 B01-10-150000 3BHE023784R1023
Honeywell TC-PPD011 51309241-125
ABB PPD115A102
Honeywell TC-PPD011
ABB PPD113B03-26-100110 3BHE023584R2634
ABB PPD113B01-10-150000 3BHE023784R1023
GE IS220PPDAH1A
Honeywell TK-PPD011
ABB 3BHE024820R0101 PPD234 A101
ABB 3BHE020570R1022 – PPD114 B1022
ABB PPD113 B01-26-111000 3BHE023784R2630
ABB PP D113 PPD113 3BHE023784R2630 B01-26-111000
ABB PPD115A02 3BHE017628R0002
ABB PPD114B1022 – 3BHE020570R1022
GE IS220PPDAH1A, REV F
IS220PPDAH1A
ABB 3BHE041576R3011 PPD517 A3011
ABB PPD113 3BHE023584R2634
ABB PPD113 B01-26-111000
ABB PPD113B01 3BHE023784R1010
ABB PPD114B Module 3BHE020570R1022
ABB 3BHE041576R3011 PPD517 A3011
ABB 3BHE024820R0101 PPD234 A101
ABB PP885 3BSE069276R1
ABB AC800F PM803F
ABB PPD104 3BHE017400R0101
More…
Leave a comment
Your email address will not be published. Required fields are marked *