The self-hosting feature is recommended only for use in FCP270s which are used with 200 Series FBMs. All of the information necessary to reboot 200 Series FBMs is included in non-volatile flash memory on the FCP270. However, the flash memory on the 100 Series FBMs and related products on the 268k fieldbus does not include this information, and they require the workstation host to be present to reboot. More details on the self-hosting feature are available in DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA).
DEVICES SUPPORTED
The FCP270 supports the following devices on the 2 Mbps module Fieldbus:
All 200 Series FBMs (FBM201, FBM202, and so forth) – both Compact and standard types
Field Device Systems Integrator (FDSI) modules
Intrinsically Safe I/O Subsystem (ISCM)
DCS Fieldbus Modules for Siemens APACS+™ Systems
DCS Fieldbus Modules for Westinghouse WDPF® Systems.
DCS Fieldbus Modules for Fisher’s PROVOX® Series 20 Migration with HART
DCS Fieldbus Modules for Honeywell® TDC 2000 Systems with HART.
The FCP270 supports the following devices on the 268 Kbps fieldbus:
100 Series FBMs (FBM01, FBM02, and so forth)
Fieldbus Cluster I/O via FBP10 fieldbus processor module
Foxboro® Hydrostatic Interface Unit (HIU)(1)
Foxboro Mass Flowmeter
Foxboro Panel Display Stations
SPECTRUM™ Migration Integrators
SPEC 200™ Control Integrators
SPEC 200 MICRO™ Control Integrators
SPEC 200 CCM Control Integrators
DCS Fieldbus Modules for Honeywell® TDC 2000 and TDC 3000 Systems
DCS Fieldbus Modules for Bailey® Net90 and Infi90 Systems
DCS Fieldbus Modules for Fisher’s PROVOX® Series 10, Series 20, and Controller Series Systems.
The Foxboro Gas Chromatograph is not supported.
BASEPLATE:The FCP270 is installed on a modular, DIN rail mounted baseplate in a dedicated slot that is keyed for the controller, so other modules cannot be placed in these slots. For further information on DIN rail mounted equipment, refer to PSS 21H-2W1 B3 and PSS 31H-2COV B3.
LED INDICATORS
Light-emitting diodes (LEDs) on the front of the FCP270 module provide visual indication of the:
FCP270 operational status
Communications activity of The MESH control network A and B links
Communications activity of fieldbus A and B
Infrared communications activity.
The MESH control network path Tx LEDs indicate which controller is primary as well as the network path it is using; these LEDs are only active on the primary module.
FUNCTIONAL SPECIFICATIONS
Processor Type
CONTROL PROCESSOR
Microprocessor-based AMD Elan 520 (running at 100 MHz) with stored programs, using highspeed communication capability. In addition, the CommControl™ ASIC with an internal 80186 controls the communication to the I/O Modules (FBMs).
Memory
SIZE
16 MB SDRAM
32 MB flash memory
ERROR DETECTION
ECC providing single-bit error detection and correction as well as multiple-bit error detection.
Process I/O Communications (with FBMs) MODULE FIELDBUS
Type
HDLC
Transmission Rate
2 Mbps for 200 Series FBMs or 268 Kbps for 100 Series FBMs
Process I/O Capacity 2 MBPS HDLC FIELDBUS
200 Series FBMs
32 maximum without FEM100 modules or with FEM100 modules, control usage supports capability for up to 128 FBMs. Refer to FCP270 Sizing Guidelines (B0700AV) for sizing constraints. Competitive Migration Modules Refer to the device specific Product Specification Sheets
268 KBPS HDLC FIELDBUS
100 Series FBMs
64 maximum depending on control processor sizing constraints (refer to FCP270 Sizing Guidelines [B0700AV]). Competitive Migration Modules Refer to the device specific Product Specification Sheets
Process I/O Capacity (Cont.)
MIX OF 2 MBPS HDLC FIELDBUS AND 268 KBPS HDLC FIELDBUS
In addition to previous sizing constraints, the total number of 100 Series and 200 Series FBMs and/or competitive migration modules supported (mixed) is 64 modules, maximum.
Memory Allocation for Blocks:5.8 MB
Maximum Number of Blocks Configured
The maximum number of blocks that can be configured for the FCP270 (or fault-tolerant FCP270 pair) is 4000.
Block Executions Per Second :10,000 blocks/second, maximum
Maximum Number of Blocks Processed
The number of blocks that can be processed per block processing cycle (BPC) time interval depends on scan periods and block type selection. These blocks include all types (control blocks, ECBs, compounds, data blocks, and so forth). For sizing guidelines, refer to FCP270 Sizing Guidelines (B0700AV).
Minimum Block Processing Cycle (BPC) :50 ms
Sequence Block Size:32 KB maximum for each block
Maximum Number of IPC Connections :131; 100 connections for source points; 30 connections for sink points; 1 connection for internal use only.
Maximum Number of OM Sink Lists:50
Maximum OM Scanner Database
12,000 points for BPC ≥ 200 ms
5,000 points for BPC ≤ 100 ms
Maximum Number of OM Sink Points :7,500
Related product recommendations:
XP POWER F7E1A6G2 10005836
A-B 802B-CPDBXSLC3802B
GE 36C774524AAG363PL
IXYS DSAI110-18F
Pro-Face PFXSP5B10 SP-5B10
ABB 64209396
Bently Nevada 3300/46
Rockwell Automation 700S-P220A1NEMA
A-B 6200V-DPDVI2
Kollmorgen TTBL 4207-B40614-0271
Bosch Rexroth R911289806
ABB DSQC653 3HAC025918-001
Baumuller BUS6-VC-AC-0069
Panasonic MADDT1207L01
Siemens 7SJ5115-4CA02-2BA0 JJ
Rexroth MAC112B-0-LD-3-C/130-A-2/S018
A-B 9301-2SE2500ESMRSView32
A-B SK-RM-PFB-F5-F6
A-B 800T-2JRH4KB7AX30mm
ABB 1VCR017053G0006